These settings define how the KNX connection should be established and by which group addresses functions are triggered.
For KNX communication at least one KNX/IP-Gateway must be located in the same network segment.
The IP-Address, connection-method, Port and KNX-medium has to be set correspondingly.
The selected connection method (tunneling or routing) must be supported by selected Gateway.
WOLi can find Gateways by clicking on the search button.
Needed information is provided and can be accepted.
From menu select ADD GA to assign a function to a group-address.
Depending on the function the datapoint Type DPT has to be:
function | value | DPT |
---|---|---|
WakeLock | On/Off | 1-bit DPT 1.001 |
Notify | ID 0…255 | 8-bit DPT5.010 |
Sound | ID 0…255 | 8-bit DPT5.010 |
Alert | ID 0…255 | 8-bit DPT5.010 |
CancelAlert | ID 0…255 | 8-bit DPT5.010 |
Speak | ID 0…255 | 8-bit DPT5.010 |
Toast | Text | 14-byte DPT16.001 |
BrowseTo | ID 0…255 | 8-bit DPT5.010 |
LaunchApp | ID 0…255 | 8-bit DPT5.010 |
SendIntent | as set | |
VolumeSystem | value 0…max | 8-bit DPT5.010 |
VolumeRing | value 0…max | 8-bit DPT5.010 |
VolumeMusic | value 0…max | 8-bit DPT5.010 |
VolumeNotification | value 0…max | 8-bit DPT5.010 |
ScreenBrightness | value 0…255 | 8-bit DPT5.010 |
HeartBeat | — | — |
BatteryLevel | 0 or KNX-READ | 8-bit DPT5.001 |
The optional input-field DPT is currently only used for SendIntent and otherwise it need not to be specified.
By selecting an existing assignment, this can be edited or deleted